Water Cooling Diesel Generator Set Power Plant , Diesel Oil Power Plant - According to the design and technical demand
Water Cooling Diesel Generator Set Power Plant , Diesel Oil Power Plant For Sale, Most Competitive Price, Fast Delivery, Custom Service, Wholesale Water Cooling Diesel Generator Set Power Plant , Diesel Oil Power Plant, Made in China, High Quality Products!, China cheap prodocuts, china suppliers Supplier, Manufacturer.?
?
- - - -
Technical specificaiton for Power plant equipments? |
Ⅰ. Gen-set technical specification |
No. | Item | Unit | Specification |
1 | Model | | 1250/2000/2500/3500GF |
2 | Rated power? | kW? | 1250/2000/2500/3500 |
3 | Rated rev. | rpm | 600 |
4 | Rated voltage | V | 11000 |
5 | Rated current? | A | 229.6 |
6 | Frequency? | Hz | 50Hz |
7 | Power factor | | 0.8 (lagging) |
8 | Phase | | 3-phase? |
9 | Voltage fluctuation rate | % | ±1 |
10 | Frequency (rev.)??fluctuation rate | % | ±0.5 |
11 | Stable voltage regulating rate | % | ±2.5 |
12 | Stable frequency (rev.) regulating rate | % | 5 |
13 | Transient?voltage?regulating rate | % | ±20~-15 |
14 | Stabilizing time | s | 5 |
15 | Voltage regulating method | | Auto? |
16 | Speed Governor | | Electronic?hydraulic |
17 | Frequency regulating method | | Auto/Manual? |
18 | Lubricating method | | Pressure lubricating |
19 | Cooling method? | | Close circuit of fresh cooling water |
20 | Coupling? | | Flexiable |
21 | Painting color | | Blue |
22 | Overall dimension | mm | 9890x2560x4015 |
23 | Net weight | kg | 75000 |
Ⅱ. Diesel engine specification |
No. | Item | Unit | Specification |
1 | Engine Model | | DN8340ZD2 |
2 | Type | | In-line, 8-Cyls, four-stroke, direct injection, charged, inter cooled |
3 | Bore | mm | 340 |
4 | Stroke? | mm | 450 |
5 | Total displacemen | L | 408.35 |
6 | Mean piston seed? | m/s | 9 |
7 | Rated power | KW | 4200 |
8 | Rated rev. | rpm | 600 |
9 | Overload??(1 hr per 12 hrs)??????????????????????? | kW/rpm | 4620/600 |
10 | Mean effective pressure | MPa | 2.56 |
11 | Compression ratio | | 13.5 |
12 | Rotation direction | | Clockwise, viewed from flywheel end. |
13 | Firing order | | 1-4-7-6-8-5-2-3 |
14 | Specific fuel oil consumption | g/kW.h | 198+3% |
15 | Specific Lube oil consumption | g/kW.h | < 1.2g/kW.h |
16 | Smoke | RB | ≤0.3 |
17 | Noise | dB(A) | 105 |
18 | Starting method | | Air Rotary valve |
19 | Cooling system | | Fresh water cooling |
20 | Lubricating system | | Pressure lubricating |
21 | Fuel oil specification | | Diesel oil and?720Cst/50℃ HFO |
22 | Lube oil specification | | CD40 with TBN according HFO |
23 | Piston lifting height | mm | 2365 |
24 | Overall dimension | mm | 7213×1850×3625mm |
25 | Net weight | kg | 47000 |
Ⅲ. Alternator specification |
No. | Item | Unit | Specification |
1 | Alternator Model | | TFW3800 |
2 | Type | | Brushless??generator |
3 | Rated power | kW? | 3500 |
4 | Rated voltage | V | 11000 |
5 | Rated current | A | 229.6 |
6 | Frequency | Hz | 50 |
7 | Power factor | | 0.8 (lagging) |
8 | Working condition | | Continuous |
9 | Phase and connection | | 3-phase |
10 | Voltage regulation method | | Brushless, self excited |
11 | Insulation Class | | F |
12 | Protection Class | | IP23 |
Ⅳ Cooling tower?specification |
No. | Item | Unit | Specification |
1 | Cooling tower model | | GBL-150 |
2 | Inlet temperature | ℃ | 60 |
3 | Outlet? | ℃ | 35 |
4 | Base Plane?Size | mm | Ф4460×5095 |
5 | Blade amount | | 4 |
6 | Fan diameter | mm | Ф3400 |
7 | Motor fan power | kW | 11 |
8 | Inlet pipe demension | mm | DN200 |
9 | Outlet pipe demension | mm | DN250 |
- - - -
?
- - - -
G300 Statinary Generating Sets Main Specification |
Model | 1000GF1 | 1250GF3 | 1350GF4 | 1400GF4 |
Rated power, KW | 1000 | 1250 | 1350 | 1400 |
Overload , KW | 1100 | 1375 | 1485 | 1540 |
Rated voltage, V | 400/415/440/3300/6300/10500/13800 |
Rated current , A | | | | | | | | |
Frequency , Hz | 50 | 60 | 50 | 60 | 50 | 60 | 50 | 60 |
Power factor | 0.8 Lagging |
Phase | 3 |
Diesel engine | G6300ZD6 | G6300ZD8 | G8300ZD6 | G6300ZD10 | G8300ZD10 | G8300ZD8 | G8300ZD10 | G8300ZD8 |
Rated power, KW | 1103 | 1470 | 1471 | 1471 | 1765 | 2000 | 1765 | 2000 |
Rated rev, rpm | 500 | 600 | 500 | 600 | 500 | 600 | 500 | 600 |
Alternator | 3 phase alternator |
voltage fluctuation rate% | <0.5 | <0.5 |
Frequency fluctuation rate, % | <0.5 | <0.5 |
Stable voltage regulating rate, % | ±1.0 | ±1.0 |
Transient voltage regulating rate, % | +20, -15 | +20, -15 |
Stable Frequency fluctuation rate, % | <3 | <0.5 |
Transient frequency regulating rate, % | +12, -10 |
Stablizing time, voltage , S | <4 |
Stablizing time, frequency , S | <3 |
voltage regulating method | automatic and munual |
Frequency regulating method | manual |
starting method | compressed air |
Lubricating method | pressue lubricating? |
Cooking method | water cooling |
coupling | flexible |
Overdimension, mm | 3880*2150*3180 | 8470*2360*3060 |
Weight, Kg | 30000 | 35000 | 38000 |
- - - -
- - - -
G300 Statinary Generating Sets Main Specification |
1500GF6 | 1600GF5 | 1800GF7 | 2000GF8 |
1500 | 1600 | 1800 | 2000 |
1650 | 1760 | 1980 | 2200 |
400/415/440/3300/6300/10500/13800 |
| | | | | | | |
50 | 60 | 50 | 60 | 50 | 60 | 50 | 60 |
0.8 Lagging |
3 |
G8300ZD10 | G8300ZD8 | G8300ZD10 | G8300ZD8 | G8300ZD8 | G8300ZD8 | G8300ZD12 | G8300ZD8 |
1765 | 2000 | 1765 | 2000 | 2000 | 2000 | 2206 | 2000 |
500 | 600 | 500 | 600 | 600 | 600 | 600 | 600 |
3 phase alternator |
<0.5 |
<0.5 |
±1.0 |
20, -15 |
<0.5 |
+20, -15 |
<5 |
<4 |
automatic and munual |
manual |
compressed air |
pressue lubricating? |
water cooling |
flexible |
8470*2360*3060 |
38000 | 42560 |
- - - -
?
?
Remark
?
1.the generator voltage and frequency can be selected
2.rating for the generator set is based on the following standard conditions
air temperature :25℃
total barometric pressure 100kpa
charge air coolant temperature 25℃
relative humidity 30%
If test ambient conditions are not same as the standard ambient conditions, the power and fuel consumptions should be revised according to GB/T6072.1-2000
3.The generator set can operate under overload, intermittently for 1 hour every 12h, the fuel injection quantity is usualy locked in the rated power position
?
- - - -
GN8320 Stationary Generating Sets Main Specification |
Model | 2400GF | 2500GF |
Rated power, KW | 2400 | 2500 |
Overload , KW | 2640 | 2750 |
Rated voltage, V | 400 | 415 | 3300 | 6300 | 10500 | 400 | 415 | 3300 | 6300 | 10500 |
Rated current , A | 4330 | 4174 | 525 | 275 | 165 | 4511 | 4348 | 547 | 172 | 286 |
Frequency , Hz | 50 | 50 |
Power factor | 0.8 Lagging | 0.8 Lagging |
Phase | 3 | 3 |
Diesel engine | GN832000ZD | GN8320ZD |
Rated power, KW | 2648 | 2795 |
Rated rev, rpm | 750 | 750 |
Alternator | 3 phase alternator |
voltage fluctuation rate% | ±1.0 |
Frequency fluctuation rate, % | +12, -10 |
Stable voltage regulating rate, % | 3 |
Transient voltage regulating rate, % | +12, -10 |
Stable Frequency fluctuation rate, % | 4 ? |
Transient frequency regulating rate, % | 5 |
Stabilizing time, voltage , S | +1 |
Stabilizing time, frequency , S | +12, -10 |
voltage regulating method | automatic and manual |
Frequency regulating method | manual |
starting method | compressed air |
Lubricating method | pressure lubricating |
Cooking method | water cooling |
coupling | flexible |
Overdimension, mm | 8950*2570*6050 |
Weight, Kg | 45000 |
- - - -
?
?
Remark
?
1.the generator voltage and frequency can be selected
2.rating for the generator set is based on the following standard conditions
air temperature :25℃
total barometric pressure
charge air coolant temperature
relative humidity
If test ambient conditions are not same as the standard ambient conditions, the power and fuel consumptions should be revised according to GB/T6072.1-2000
3.The generator set can operate under overload, intermittently for 1 hour every 12h, the fuel injection quantity is usualy locked in the rated power position
?
Wuxi Kangwei Environment & Energy Equipment Co., Ltd
Address: NO.8, YINGHUI ROAD, Wuxi, Jiangsu, China, 214000
Tel: 86-510-85990011
Wuxi Kangwei Environment and Energy Equipment Co.,Ltd, like a shining pearl ,located alongside the beautiful sight of TaiHu lake of Wuxi. With the many years accumulated mature development in the designing, manufacturing and management, the business range had included the large power diesel engine generator set and relevant auxiliary fuel oil system equipment as well as the environment protection
Our company had passed the international quality system identification, such as ISO14001and ISO9001. All equipments which designed and manufactured by us apply to the system of diesel engine genset and landbased HFO fired power plant, specialize in manufacturing diesel engine generator set ,combined LO/cooling water module, combined fuel oil and LO system treatment module, fuel oil booster unit, different type of oil filter controlled by manual and automatic, oil separator unit, boiler system, most of the products with good reputation in the market and have recognized by the international classification society at home and abroad, such as CCS,BV,ABS,ASME etc ,had become a one-stop integrated solutions provider for the marine power system and HFO power station
Wuxi Kangwei also mainly focuses on the development of environment protection businesses especially the environment energy and water, developed the integrated ability for the environment technology designing, development, currently have the enough specialized ability to finish the environment project construction and engineering, such as waste-to-energy, biomass power generation
Kangwei will positively continue to promote the healthy and good development for the system of diesel engine genset and environment protection, expect to build up good business cooperation with you in the future with our higher quality services.