origin China
packaging Plywood Casing or standard package suitable for sea and air transport
MOQ: 1
Glycol Water Chiller with the cooling capacity from 60kW~260kW. This Type Water Chiller mainly used in the low temperature condition, such as brewage industriy, beverage industriy etc. Low temperature Water Chiller can work indenpendently or together with up to 16 slave modulars. The Air Cooled Water Chiller with compact design, reaso
nable layout and co
nvenient for installation & maintenance etc. Amrta chillers not o
nly serve Cooling and Heating System, also cooling machine to make the machine running at a good condition, low operating costs with superior energy efficiency levels.
Application areas
● Offices, Hotels, Hospitals, Industry
● Administration
● Light commercial and residential buildings
Why this choice?
● Very high efficiency with R410A
● Very low noise operation
● R410A scroll compressors
● Advanced co
ntrol
● Unit with pump and optio
nal buffer tank
● Very compact for outdoor or indoor installation
Characteristics
The master module can work independently or together with up to 16 slave modules.
Air co
nditioner of chillers with V type heat exchanger: panels, f
rame and ba
se are made from galvanized steel protected with polyester powder painting to ensure total resistance to atmospheric agents.
3-phase scroll type compressor, with builtin thermal overload cut-out and crankcase heater, mounted on rubber vibration dampers.
External rotor type axial fans, equipped with three phase direct drive motors, low noise 8 poles, protection level IP54, provided with a protective outlet grille.
Evaporator built with high efficiency shell and tube type heat exchanger, factory insulated with flexible close cell material.
Co
ndenser built with seamless copper tubes mechanically expanded into blue hydro
philic aluminum fins.
Refrigerant circuit complete with charge valves, filter drier, sight glass, gas-liquid separator, thermostatic expansion valve, high & low pressure switch. The heat pump unit is completed also with 4-way valve, liquid receiver and one way valve.
Hydraulic circuit built with galvanized pipe, complete with water discharge co
nnection for tube in tube heat exchanger and flange type hydraulic co
nnectors in two directions easy for co
nnections from both sides of the units.
Electric panel co
nsist of:
Compressor contactor, fan motor contactor, compressor protection breaker, fan protection breaker, phase sequence relay and microprocessor with function display (display o
nly for master/packaged unit)
Automatic operation dramatically reducing maintenance cost thanks to reliable microprocessor system.
Optio
nal
Paddle flow switch;
me
tallic filter for hydraulic circuit;
Water pump;
Rubber antivibration mounting;
Heat recovery functions.
Technical Data
Model AW
60
100
130
200
260
Cooling capacity*
kW
65
97.5
130
195
260
Cooling power input
kW
20.8
31.4
42.1
63.6
84.2
Heating capacity**
kW
68
102
136
204
272
Heating power input
kW
20.2
30.6
41
61.2
82
Max Input Power
kW
24
35.7
47.7
71.4
95.4
Max Input current
A
50
74
97
148
194
Cooling Running Current
A
46
68
89
136
178
Start-Up Current
A
167
187
206
374
412
Compressor
Power supply
/
380/3/50
Brand/Type
/
Daikin/Scroll
Refrigerant
/
R410a
Qty/refrigerant circuit
Nr.
2
3
4
6
8
Cooling power input*
kW
2*9.4
3*9.63
4*9.77
6*9.63
8*9.77
Heating power input**
kW
2*9.1
3*9.36
4*9.5
6*9.36
8*9.5
Energy adjustment
%
0-25-50-75-100
Axial fan
Quantity
Nr.
2
2
2
4
4
Power input
kW
2
2.5
3
5
6
Airflow
m3/h
24000
36000
48000
72000
96000
Evaporator
Type
/
Shell and tube heat exchanger
Water flow when cooling
m3/h
11.2
16.8
22.4
33.6
44.8
Water flow when heating
m3/h
11.7
17.6
23.4
35.1
46.8
Water side pressure drop ***
kPa
46
52
55
52
55
Water co
nnection size
DN
50
50
65
2x50
2x65
Noise level***
dB(A)
70
72
72
74
75
Dimensions
V type coil
Length
mm
2000
2207
2207
2207
2207
Width
mm
1060
1300
1300
2207
2207
Height
mm
1957
2076
2076
2096
2096
Net weight
kg
620
1060
1120
2160
2280
Working weight
kg
635
1090
1155
2220
2350
*Ambient temperature 35ºC; evaporator water in/out 12/7 ºC;
** Ambient temperature DB 7 ºC, WB 6 ºC; co
ndenser water in/out temperature 40/45 ºC;
*** In the nominal water flow condition the pressure drop is between this range.
**** Sound pressure measured at a distance of 1 m and a height of 1.5 m above the ground in a dear field.
http://www.amrtaac.com
Tags: Glycol Chiller Cooling System,Low Temperature Scroll Chiller,Low Temperature Glycol Chiller